Low- Med Static Ceiling Concealed Series

Low- Med Static Ceiling Concealed Series

Low- Med Static Ceiling Concealed Series

The Low-Med Static Ceiling Concealed Series is a high-efficiency concealed chilled water fan coil unit designed for quiet operation and seamless ceiling integration. Ideal for hotels, offices, and healthcare spaces, it delivers reliable airflow performance while remaining hidden from view.

Applications
Applications
Applications
  • Concealed ceiling-suspended chilled water fan coil unit

  • Designed for high efficiency and quiet operation

  • Seamlessly integrates within concealed ceiling spaces

  • Ideal for hotels, offices, and hospital rooms

Technical Specification

Ceiling Concealed Series (3 Rows)

Brand
BRIA
Category
Duct Type
Model Range
BDF-3R-2P-300
Series
Standard Cooling
ParametersLabelSubUnitBDF-3R-2P-300
Air FlowHCMH510
MCMH410
LCMH270
Cooling CapacityHTHkW3.09
HSHkW2.19
Water Flowlph530
Sound Pressure LevelHdB(A)41
MdB(A)37
LdB(A)31
Note
  • Cooling Condition: Entering water 7°C, Outlet water 12°C, Entering air temp. 27°C DBT / 19.5°C WBT
  • Heating Condition: Entering water 60°C, Entering air temp 21°C DBT, water flow same as cooling
  • Noise is tested in full-anechoic test room at distance of 1m.
  • Airflow & performance data is based on ESP 12Pa
  • H: High speed; M: Medium speed; L: Low speed; TH: Total cooling; SH: Sensible cooling
  • Specification are subject to change due to continuous R&D upgradation
Technical Specification

Ceiling Concealed Series (4 Rows)

Brand
BRIA
Category
Concealed
Model Range
BDF-4R-2P-300
Series
Standard Cooling
ParametersLabelSubUnitBDF-4R-2P-300
Air FlowHCMH485
MCMH390
LCMH245
Cooling CapacityHTHkW3.4
HSHkW2.3
Water Flowlph580
Sound Pressure LevelHdB(A)43
MdB(A)39
LdB(A)33
Note
  • Cooling Condition: Entering water 7°C, Outlet water 12°C, Entering air temp. 27°C DBT / 19.5°C WBT
  • Heating Condition: Entering water 60°C, Entering air temp 21°C DBT, water flow same as cooling
  • Noise is tested in full-anechoic test room at distance of 1m.
  • Airflow & performance data is based on ESP 12Pa
  • H: High speed; M: Medium speed; L: Low speed; TH: Total cooling; SH: Sensible cooling
  • Specification are subject to change due to continuous R&D upgradation
Technical Specification

Ceiling Concealed Series (3+1 Rows)

Brand
BRIA
Category
Concealed
Model Range
BDF-(3+1)R-2P-300
Series
Standard Cooling
ParametersLabelSubUnitBDF-(3+1)R-2P-300
Air FlowHCMH485
MCMH390
LCMH245
Cooling CapacityHTHkW3.09
HSHkW2.19
Water Flowlph530
Sound Pressure LevelHdB(A)43
MdB(A)39
LdB(A)33
Note
  • Cooling Condition: Entering water 7°C, Outlet water 12°C, Entering air temp. 27°C DBT / 19.5°C WBT
  • Heating Condition: Entering water 60°C, Entering air temp 21°C DBT, water flow same as cooling
  • Noise is tested in full-anechoic test room at distance of 1m.
  • Airflow & performance data is based on ESP 12Pa
  • H: High speed; M: Medium speed; L: Low speed; TH: Total cooling; SH: Sensible cooling
  • Specification are subject to change due to continuous R&D upgradation
Technical Specification

Product Dimensions

*All dimensions are in mm
ParametersLabel30040050060080010001200140016002000
Body DimensionL955105511551255165517551895189517552015
H250250250250250250250250300300
W546546546546546546546546616616